Where vendors provide recommendations for site storage and protection these are to be followed and take precedence over the following recommendations.
Where prolonged site storage is involved, which is not under the control of vendors, equipment guarantees are invalidated. However most vendors offer a re-furbishing service after which equipment guarantees are re-instated. Such a service is outside normal Company contracts but clients are recommended to take up this option where applicable at their own expense.
A warm, clean, dry and vibration free environment in a secure under cover storage area is required. Recommended environment conditions are temperature range of 15°C to 30°C and a humidity of between 30 to 40%.
Instruments can be stored in the above environment for up to 4 months in their shipment cases. However, where cases/packing have been opened the plastic coverings are to be retained and resealed in the manner they were shipped.
Where moisture absorbents are included they are to be replace with the new charge on receipt on site and further replaced at regular intervals thereafter.
Adjacent 220 and 110 volt supply made available for energizing equipment as necessary.
Panels to be stored up-right and level, any temporary transportation/strengthening supports to be reinstated and maintained.
Threaded connections to be re-capped and rust protected, also maintained.
Ensure all Nameplates/Tags/Gland plates are intact and secure, also maintain.
All openings shall be tightly plugged against entry of water.
The power pack units of the control panel racks shall be energized at monthly intervals. For storage in original packing refer to recommendation of vendor.
panel instruments
distribution control components
racks with power supply and/or cards
computer racks and components
programmable controllers
will be stored in air conditioned spaces.
transmitters I/P
converters, and others
will be stored shielded from direct sun radiation.
Refer to vendor's recommendations.
Safety valves shall be stored in the warehouse and either dummies installed in the line or the lines blanked off.
The valves shall be stored indoors in a clean, dry environment. Avoid extreme temperatures and humidity conditions.
Threaded connections to the capped and rust protected.
Ensure all Nameplates/Tags/Gland plates are intact and secure, also maintain.
For stainless steel safety valves special instructions should be followed.
Stainless steel (alloys containing more than 10% chromium) equipment, components, and materials shall be protected as follows:
Indoor storage,
Not in contact with the soil or with porous supports such as raw wood. Protective coatings are acceptable alternatives to covered storage.
In addition, austenitic stainless steels shall not be exposed to salt water or salt spray.
Internals of carbon steel relief valves are to be treated with Shell Ensis.